Shut-off valve control panel

Shut-off valve control panel VC100

A control panel designed for direct installation in the plumbing network that controls up to two motorized valves and automatically shuts them off when a leak is detected.

Product

VC100 control panel overview

The VC100 is a control panel for automatic water shut-off valves, designed for direct installation in the plumbing network. It controls up to two motorized valves, such as the MBV110, and receives signals from an optional water leak detector or flow meters to trigger automatic water shut-off as soon as a problem is detected.

Connected to the LoRaWAN® network and the Oblik platform, it sends real-time valve status and enables remote adjustment of automation rules.

Benefits

Key advantages of the VC100

The VC100 centralizes valve control, maintains protection during critical conditions and gives an immediate view of system status.

Centralized control

Controls up to two motorized valves from one device to protect a floor, zone or unit.

Integrated frost protection

Automatically closes valves below 2 °C to reduce the risk of freezing in monitored areas.

Continuity and visibility

The optional backup battery maintains protection during an outage; the action button and status lights provide an immediate view of valve status.

Features

VC100 features and specifications

The VC100 combines valve control, protective triggers and LoRaWAN® connectivity to automate water shut-off while keeping the system visible.

Controls two valves

Controls up to two 9-24 VDC motorized valves from 1/2 to 2 in., with position confirmation.

Automatic shut-off triggers

Triggers shut-off on leak detection through a dedicated port for an optional detection probe, or on a flow-meter signal.

Frost protection and backup power

Automatically closes below 2 °C and reactivates above 5 °C. The optional UPS012 battery provides up to 6 days of backup for one valve or 3 days for two valves.

Accessible connection and control

Communicates by LoRaWAN® up to 16 km in rural areas and 5 km in urban areas. The action button and status lights simplify control and diagnostics without an app.

VC100 technical specifications

Model: VC100 – Shut-off valve control panel

Dimensions: 100 × 60 × 25 mm – white ABS plastic enclosure

Connectivity: LoRaWAN® wireless – range up to 16 km (rural) / 5 km (urban), remote control through Oblik

Power supply: 9 to 24 VDC – supplied 12 VDC/2 A power supply

Backup battery: UPS012 (optional) – up to 6 days for 1 valve, 3 days for 2 valves

Valve compatibility: Up to 2 motorized 9-24 VDC valves, 1/2 to 2 in. ball valves, 6-wire or 5-wire actuators with position confirmation

Inputs/outputs: 2 valve connectors, 1 port for an optional leak-detection probe, 2 flow-meter connectors, 1 DC power connector, 1 action button

Temperature range: 0 to 60 °C – humidity ≤ 95% non-condensing

Compliance and certifications: Complies with ICES-003, Class B. Contains a certified radio module: IC: 25908-RAK3172; FCC ID: 2AF6B-RAK3172. Supplied power adapter is cETLus certified to CSA C22.2 No. 223:2015 (Class 2).

Warranty: 2 years, limited

Installation

How to install the VC100

Install the VC100 directly on the plumbing network, then verify the valves and LoRaWAN® connection are operating correctly.

Connect the valves

Connect one or both motorized valves to the VC100 before powering it on. Always use the supplied 12 VDC/2 A power supply.

Commissioning

Once powered, the VC100 starts an initialization cycle that can take up to 30 seconds, including an automatic closure to confirm the position of detected valves. Confirm that the blue light indicates the LoRaWAN® connection.

Placement

Mount the device on a wall, on the plumbing or flat, directly on the plumbing network. Avoid large metal objects nearby, which can interfere with the LoRaWAN® connection.

Verification

Use the action button to test opening and closing of the connected valves. A valve not detected at startup is excluded from commands until the next restart.

VC100 control panel FAQ

Up to two 9-24 VDC motorized valves, from 1/2 to 2 in., with position confirmation.

With the optional UPS012 backup battery, the VC100 continues operating for up to 6 days with one valve or 3 days with two valves. An integrated supercapacitor can also send up to three alerts before complete shutdown.

Yes. Valves close automatically when the temperature falls below 2 °C, using the default threshold, and reactivate above 5 °C.